EasyManua.ls Logo

ABB RER670 - Page 93

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InvW2Curr=No
Then the internal calculations will be:
1
12
1
12
100 100
% IDLW1 IDLW2
100 100
% 1 , 2 ,
Diff V S
BaseW BaseW
Bias V S
BaseW BaseW
I I I
II
I Max IDLW IDLW Max I I
II





IECEQUATION203 V2 EN-US (Equation 10)
The phase selection settings for the second instance of the T1PPDIF function shall
be:
PhSelW1=L2
PhSelW2=L1
InvW2Curr=Yes
Then the internal calculations will be:
2
12
2
12
100 100
% IDLW1 IDLW2
100 100
% 1 , 2 ,
Diff U S
BaseW BaseW
Bias U S
BaseW BaseW
I I I
II
I Max IDLW IDLW Max I I
II





IECEQUATION204 V2 EN-US (Equation 11)
Transformer connection – example 3
GUID-945C3857-BE28-484D-B68F-7C9C3BB05441 v2
IEC150001 72-2-en.vsdx
132/66kV
66kV132kV
I
U
v
I
U
I
S
S
V
I
R
R
IEC15000172 V2 EN-US
Figure 34: Transformer connection – example 3
The HV currents I
V
and I
U
shall be connected as IL1 and IL2 currents, respectively,
for the winding 1 side towards the T1PPDIF function. The LV currents I
S
and I
R
shall be connected as IL1 and IL2 currents, respectively, for the winding 2 side
towards the T1PPDIF function.
1MRK 506 375-UEN A Section 6
Differential protection
Railway application RER670 2.2 IEC 87
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals