2.3.1.11  CTRL.ESSXSWI1 Earthing switch indication (1)
Table 14: CTRL.ESSXSWI1 Earthing switch indication (1)
BitA
RegA IEC 61850 name SA name Description Values
    CTRL.ESSXSWI1 POSITION    
2801 175.01 .Pos.stVal.Close - Close bit 1=Close
2802 175.02 .Pos.stVal.Open - Open bit 1=Open
2803 175.03 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.12  CTRL.ESSXSWI2 Earthing switch indication (2)
Table 15: CTRL.ESSXSWI2 Earthing switch indication (2)
BitA RegA IEC 61850 name SA name Description Values
    CTRL.ESSXSWI2 POSITION    
2807 175.07 .Pos.stVal.Close - Close bit 1=Close
2808 175.08 .Pos.stVal.Open - Open bit 1=Open
2809 175.09 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.13  CTRL.ESXSWI1 Earthing switch control (1)
Table 16: CTRL.ESXSWI1 Earthing switch control (1)
BitA
RegA IEC 61850 name SA name Description Values
    CTRL.ESXSWI1 POSITION    
3496 218.08 .Pos.stVal.Close - Close bit 1=Close
3497 218.09 .Pos.stVal.Open - Open bit 1=Open
3498 218.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3499 218.11 .Pos.stSeld - Control selected 1=Selected
    CTRL.ESCILO1      
3500 218.12 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3501 218.13 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
    CTRL.ESXSWI1      
3502 218.14 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3503 218.15 .mcd      
3504 219.00 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3505 219.01 .mcd      
    CTRL.ESCILO1      
3506 219.02 .ItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
3507 219.03 .mcd      
1MRS756878 H Section 2
Modbus data mappings
RET615 21
Point List Manual