0xA CS IEC 61850 name SA name Description Values
2147 7.03 .Pos.Oper.ctlVal Execute selection 1=Execute
2148 7.04 .Pos.Oper.ctlVal Direct open 1=Open
2149 7.05 .Pos.Oper.ctlVal Direct close 1=Close
2.5.4 CTRL.DCXSWI2 Disconnector control (2)
Table 168: CTRL.DCXSWI2 Disconnector control (2)
0xA CS IEC 61850 name SA name Description Values
CTRL.DCCSWI2
2150 7.06 .Pos.Oper.ctlVal Select open 1=Select
2151 7.07 .Pos.Oper.ctlVal Select close 1=Select
2152 7.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2153 7.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2154 7.10 .Pos.Oper.ctlVal Direct open 1=Open
2155 7.11 .Pos.Oper.ctlVal Direct close 1=Close
2.5.5 CTRL.ESXSWI1 Earthing switch control (1)
Table 169: CTRL.ESXSWI1 Earthing switch control (1)
0xA
CS IEC 61850 name SA name Description Values
CTRL.ESXSWI1
2054 1.06 .Pos.Oper.ctlVal Select open 1=Select
2055 1.07 .Pos.Oper.ctlVal Select close 1=Select
2056 1.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2057 1.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2058 1.10 .Pos.Oper.ctlVal Direct open 1=Open
2059 1.11 .Pos.Oper.ctlVal Direct close 1=Close
2.5.6 LD0.LDEV1 Protection relay's warm reset (1)
Table 170: LD0.LDEV1 Protection relay's warm reset (1)
0xA
CS IEC 61850 name SA name Description Values
LD0.LDEV1
2080 3.00 .WrmStrCmd.Oper.ctlVal Warm reboot of protection relay 1=Reboot
Section 2 1MRS756878 H
Modbus data mappings
86 RET615
Point List Manual