RegA Type Scale IEC 61850 name SA name Description Values
2044 u16 -     Minute - second  
2045 u16 -     Milliseconds  
2046 u16 -     Time quality  
             
2047 u16 1000 .MaxAmpsC.mag Max demand IL3 Max. phsC demand
0.00...40.0
[xIn]
          Update time stamp see doc.
2048 u16 -     Year - month  
2049 u16 -     Day - hour  
2050 u16 -     Minute - second  
2051 u16 -     Milliseconds  
2052 u16 -     Time quality  
2.4.1.32  LD0.CMMXU2 Three-phase current measurement (2)
Table 135: LD0.CMMXU2 Three-phase current measurement (2)
RegA Type Scale IEC 61850 name SA name Description Values
      LD0.CMMXU2   Phase current (2)  
152 u16 1000 .A.phsA.instCVal.mag I_INST_A Phs A amplitude
0.00...40.0
[xIn]
153 u16 1000 .A.phsB.instCVal.mag I_INST_B Phs B amplitude
0.00...40.0
[xIn]
154 u16 1000 .A.phsC.instCVal.mag I_INST_C Phs C amplitude
0.00...40.0
[xIn]
2.4.1.33  LD0.CSMSQI1 Sequence current measurement (1)
Table 136: LD0.CSMSQI1 Sequence current measurement (1)
RegA
Type Scale IEC 61850 name SA name Description Values
      LD0.CSMSQI1   Sequence of currents  
142 u16 1000 .SeqA.c1.instCVal.mag I1_INST Positive amplitude
0.00...40.0
[xIn]
143 u16 1000 .SeqA.c2.instCVal.mag I2_INST Negative amplitude
0.00...40.0
[xIn]
144 u16 1000 .SeqA.c2.instCVal.mag I3_INST Zero amplitude
0.00...40.0
[xIn]
Section 2 1MRS756878 H
Modbus data mappings
74 RET615