EasyManua.ls Logo

ABB RET615 - LD0.RESVMMXU1 Residual Voltage Demand Value (1); LD0.RESVMMXU1 Residual Voltage Measurement (1); LD0.SSCBR1 Circuit-Breaker Condition Monitoring (1)

ABB RET615
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.4.1.41 LD0.RESVMMXU1 Residual voltage demand value (1)
Table 144: LD0.RESVMMXU1 Residual voltage demand value (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RVAVMMXU1 Demand value
1977 u16 1000 .PhV.res.cVal.mag U_DMD_RES Residual amplitude 0.00…4.0
[xUn]
1978 Year - month
1979 Day - hour
1980 Minute - second
1981 Milliseconds
1982 Time quality
LD0.RVMAMMXU1 Max. demand value
1983 u16 1000 .PhV.res.cVal.mag Max demand Uo Residual amplitude 0.00…4.0
[xUn]
1984 Year - month
1985 Day - hour
1986 Minute - second
1987 Milliseconds
1988 Time quality
LD0.RVMIMMXU1 Min. demand value
u16 1000 .PhV.res.cVal.mag Min demand Io Residual amplitude 0.00…4.0
[xUn]
2.4.1.42 LD0.RESVMMXU1 Residual voltage measurement (1)
Table 145: LD0.RESVMMXU1 Residual voltage measurement (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RESVMMXU1 Residual voltage (1)
137 u16 1000 .A.res.instCVal.mag U0_INST - amplitude
0.00..4.00
[xUn]
2.4.1.43 LD0.SSCBR1 Circuit-breaker condition monitoring (1)
Table 146: LD0.SSCBR1 Circuit-breaker condition monitoring (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.SSCBR1
2070 u16 1 .InaTmdCnt.stVal INA_DAYS CB inactive days 0..65535
2071 u16 1 .TmmsOpn.mag T_TRV_OP Open travel time 0..60000 [ms]
2072 u16 1 .TmmsCls.mag T_TRV_CL Close travel time 0..60000 [ms]
2073 u16 100 .TmsSprCha.mag T_SPR_CHR Spring charge time
0.00…99.99
[s]
Table continues on next page