2.4.2.9  LD0.SCA4GAPC4 Analog value scaling (4)
Table 163: LD0.SCA4GAPC4 Analog value scaling (4)
RegA
Type Scale IEC 61850 name SA name Description Values
      LD0.SCA4GAPC4      
  i16 1000 .AnValOut1.mag AO1_VALUE Analog value 1 after scaling 0…N
  i16 1000 .AnValOut2.mag AO2_VALUE Analog value 2 after scaling 0…N
  i16 1000 .AnValOut3.mag AO3_VALUE Analog value 3 after scaling 0…N
  i16 1000 .AnValOut4.mag AO4_VALUE Analog value 4 after scaling 0…N
2.5  Controls
Table 164: Explanations of the controls table columns
Column name Description
0xA Coil (0X) address for control value.
CS Control structure and bit within the structure for control value.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the written value.
2.5.1  Reset, acknowledge and trigger points
Table 165: Reset, acknowledge and trigger points
0xA
CS IEC 61850 name SA name Description Values
    LD0.LLN0      
2060 2.00 .LEDRs1.Oper.ctlVal   Reset indications and LEDs 1=Reset
2061 2.01 .LEDRs2.Oper.ctlVal   Reset alarm LEDs 1=Reset
    LD0.PEMMXU1      
2062 2.02 .RecRs.Oper.ctlVal   Reset power max demands 1=Reset
2063 2.03 < reserved >      
2064 2.04 < reserved >      
    LD0.SSCBR1      
2065 2.05 .RsAccAPwr.Oper.ctlVal   Reset CB accum. energy 1=Reset
2066 2.06 .RsCBWear.Oper.ctlVal   Reset CB wear data 1=Reset
    DR.RDRE1      
2067 2.07 .RcdTrg.Oper.ctlVal   Trig DR recording 1=Trig
Table continues on next page
Section 2 1MRS756878 H
Modbus data mappings
84 RET615
Point List Manual