RegA Type Scale IEC 61850 name SA name Description Values
2074 i16 1 .RmnLifPhA.stVal CB_LIFE_A Remain.life phs A -/+ 9999
2075 i16 1 .RmnLifPhB.stVal CB_LIFE_B Remain.life phs B -/+ 9999
2076 i16 1 .RmnLifPhC.stVal CB_LIFE_C Remain.life phs C -/+ 9999
2077 u16 1 .AccAPwrPhA.mag IPOW_A Iyt phs A 0..1E6
2078 u16 1 .AccAPwrPhB.mag IPOW_B Iyt phs B 0..1E6
2079 u16 1 .AccAPwrPhC.mag IPOW_C Iyt phs C 0..1E6
2.4.1.44  LD0.T2PTTR1 Three-phase thermal overload protection, two time
constants (2)
Table 147: LD0.T2PTTR1 Three-phase thermal overload protection, two time constants (2)
RegA Type Scale IEC 61850 name SA name Description Values
      LD0.T2PTTR1      
146 i16 1 .Tmp.mag TEMP Object temperature
-100.0…
9999.9 [C]
147 u16 1 .TmpRl.mag TEMP_RL Relative temperature
0.00…99.99
[C]
2068 u16 1 .TmsOp.stVal THERMLEV_ST Est. time to operate 0...60000 [s]
2069 u16 1 .TmsRecEna.stVal THERMLEV_END Est. time to deactivate block 0...60000 [s]
2.4.1.45  LD0.TPOSYLTC1 Tap changer position indication (1)
Table 148: LD0.TPOSYLTC1 Tap changer position indication (1)
RegA
Type Scale IEC 61850 name SA name Description Values
      LD0.TPOSYLTC1      
151 i16 1 .TapPos.valWTr.posVal TAP_POS Tap changer position -64...63
2.4.1.46  LD0.TR2PTDF1 Stabilized and instantaneous differential protection for
two-winding transformers (1)
Table 149: LD0.TR2PTDF1 Stabilized and instantaneous differential protection for two-winding transformers (1)
RegA
Type Scale IEC 61850 name SA name Description Values
      LD0.TR2PTDF1   Differential current  
2080 u16 1000 .DifAClc.phsA.mag   Phs A magnitude 0...40.00 [xIn]
2081 u16 1000 .DifAClc.phsB.mag   -Phs B magnitude 0...40.00 [xIn]
2082 u16 1000 .DifAClc.phsC.mag   Phs C magnitude 0...40.00 [xIn]
      LD0.TR2PTDF1   Bias current  
2083 u16 1000 .RstA.phsA.mag   Phs A magnitude 0...40.00 [xIn]
2084 u16 1000 .RstA.phsB.mag   Phs B magnitude 0...40.00 [xIn]
2085 u16 1000 .RstA.phsC.mag   Phs C magnitude 0...40.00 [xIn]
1MRS756878 H Section 2
Modbus data mappings
RET615 79