2.4.1.22 SSR6 System status register (6) control command status (client-
dependent)
Table 125: SSR6 System status register (6) control command status (client-dependent)
RegA
Type Scale IEC 61850 name SA name Description Values
Last cmd result code
1)
133.00 Bit - bit 0
133.01 Bit - bit 1
133.02 Bit - bit 2
133.03 Bit - bit 3
133.04 Bit - bit 4
133.05 Bit - bit 5
133.06 Bit - bit 6
133.07 Bit - bit 7
Response Type
1)
133.08 Bit - bit 0
133.09 Bit - bit 1
Command state
1)
133.10 Bit - bit 0
133.11 Bit - bit 1
Cmd sequence number 0...15
133.12 Bit - bit 0
133.13 Bit - bit 1
133.14 Bit - bit 2
133.15 Bit - bit 3
1) See the technical manual.
2.4.1.23 System diagnostic values
Table 126: System diagnostic values
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.LPHD1
2060 u16 1 .PhyHealth1.stVal Warning Last warning code
1)
2061 u16 1 .PhyHealth2.stVal Internal fault Last internal fault code
1)
DR.RDRE1
2062 u16 1 .FltNum.stVal Num. of DR recordings 0...N
2063 u16 1 .MemUsed.stVal DR memory used 0...100 [%]
LD0.LPHD1
2064 u16 1 .NumPwrUp.stVal Num. of cold starts 0...65535
2065 u16 1 .WrmStr.stVal Num. of warm starts 0...65535
Table continues on next page
1MRS756878 H Section 2
Modbus data mappings
RET615 69
Point List Manual