2.3.1.46  LD0.PHLPTOC1 Three-phase non-directional overcurrent protection,
low stage (1)
Table 49: LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.PHLPTOC1      
2880 180.00 .Str.general START General start 1=Start
2881 180.01 .mcd      
2882 180.02 .Str.phsA   Phs A start 1=Start
2883 180.03 .mcd      
2884 180.04 .Str.phsB   Phs B start 1=Start
2885 180.05 .mcd      
2886 180.06 .Str.phsC   Phs C start 1=Start
2887 180.07 .mcd      
2888 180.08 .Op.general OPERATE General operate 1=Operate
2889 180.09 .mcd      
2.3.1.47  LD0.PHLPTOC2 Three-phase non-directional overcurrent protection,
low stage (2)
Table 50: LD0.PHLPTOC2 Three-phase non-directional overcurrent protection, low stage (2)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.PHLPTOC2      
2910 181.14 .Str.general START General start 1=Start
2911 181.15 .mcd      
2912 182.00 .Str.phsA   phsA start 1=Start
2913 182.01 .mcd      
2914 182.02 .Str.phsB   phsB start 1=Start
2915 182.03 .mcd      
2916 182.04 .Str.phsC   phsC start 1=Start
2917 182.05 .mcd      
2918 182.06 .Op.general OPERATE General operate 1=Operate
2919 182.07 .mcd      
Section 2 1MRS756878 H
Modbus data mappings
34 RET615
Point List Manual