2.3.2.2 Common data 2
Table 78: Common data 2
BitA
RegA IEC 61850 name SA name Description Values
LD0.LDEV1
.StLstOv.stVal Internal ind. overflow 1=Overflow
.mcd
.MeasLstOv.stVal Internal meas. overflow 1=Overflow
.mcd
.ChgFlg.stVal Configuration changed 1=Changed
.mcd
.FacSet.stVal Factory settings in use 1=In use
.mcd
LD0.GNRLLTMS1
.TmChSt1.stVal Time synch. status 0/1=Down/Up
.mcd
LD0.SCHLCCH1
.ChLiv.stVal CH1LIV Ethernet channel 1 live 1=Live
.mcd
LD0.SCHLCCH2
.ChLiv.stVal CH2LIV Ethernet channel 2 live 1=Live
.mcd
LD0.SCHLCCH3
.ChLiv.stVal CH3LIV Ethernet channel 3 live 1=Live
.mcd
2.3.2.3 LD0.DIAGLCCH1 Ethernet supervision (1)
Table 79: LD0.DIAGLCCH1 Ethernet supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.DIAGLCCH1
.ChLiv.stVal CHLIV Ethernet channel live 1=Live
.mcd
.RedChLiv.stVal REDCHLIV Red. Ethernet channel live 1=Live
.mcd
1MRS756878 H Section 2
Modbus data mappings
RET615 47
Point List Manual