BitA RegA IEC 61850 name SA name Description Values
3141 196.05 .mcd      
3142 196.06 .Str.phsB   Phs B start 1=Start
3143 196.07 .mcd      
3144 196.08 .Str.phsC   Phs C start 1=Start
3145 196.09 .mcd      
3146 196.10 .Op.general OPERATE General operate 1=Operate
3147 196.11 .mcd      
2.3.1.51  LD0.PHPTUV2 Three-phase undervoltage protection (2)
Table 54: LD0.PHPTUV2 Three-phase undervoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
    LD0.PHPTUV2      
3148 196.12 .Str.general START General start 1=Start
3149 196.13 .mcd      
3150 196.14 .Str.phsA   Phs A start 1=Start
3151 196.15 .mcd      
3152 197.00 .Str.phsB   Phs B start 1=Start
3153 197.01 .mcd      
3154 197.02 .Str.phsC   Phs C start 1=Start
3155 197.03 .mcd      
3156 197.04 .Op.general OPERATE General operate 1=Operate
3157 197.05 .mcd      
2.3.1.52  LD0.RESCMMXU1 Residual current measurement (1)
Table 55: LD0.RESCMMXU1 Residual current measurement (1)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.RESCMMXU1      
2760 172.08 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2761 172.09 .mcd      
2762 172.10 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2763 172.11 .mcd      
Section 2 1MRS756878 H
Modbus data mappings
36 RET615
Point List Manual