EasyManua.ls Logo

ABB RET615 - LD0.TRPPTRC5 Master Trip (5); LD0.UL1 TVTR1 Three-Phase VT Supervision (1); Registers

ABB RET615
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.2.25 LD0.TRPPTRC5 Master trip (5)
Table 101: LD0.TRPPTRC5 Master trip (5)
BitA
RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC5
.Op.general Op. input signal 1 = Operate
.mcd
.Tr.general Trip output signal 1 = Trip
.mcd
2.3.2.26 LD0.UL1TVTR1 Three-phase VT supervision (1)
Table 102: LD0.UL1TVTR1 Three-phase VT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.UL1TVTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.4 Registers
Table 103: Explanations of columns in register tables
Column name
Description
RegA Default 3X and 4X register address for the data.
Type Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits integer)
or i16, i32 (signed 16 and 32 bit integer).
Scale Scale factor as default. Also, an adjustable offset value exists that is set to 0 by
default.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information. Also,
if a register is writable, it is stated here.
Values The value range of the original IEC 61850 value, that is, before scaling.
Section 2 1MRS756878 H
Modbus data mappings
54 RET615
Point List Manual

Table of Contents

Other manuals for ABB RET615

Related product manuals