2.3.1.42 LD0.PHHPTOC1 Three-phase non-directional overcurrent protection,
high stage (1)
Table 45: LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC1
2890 180.10 .Str.general START General start 1=Start
2891 180.11 .mcd
2892 180.12 .Str.phsA Phs A start 1=Start
2893 180.13 .mcd
2894 180.14 .Str.phsB Phs B start 1=Start
2895 180.15 .mcd
2896 181.00 .Str.phsC Phs C start 1=Start
2897 181.01 .mcd
2898 181.02 .Op.general OPERATE General operate 1=Operate
2899 181.03 .mcd
2.3.1.43 LD0.PHHPTOC2 Three-phase non-directional overcurrent protection,
high stage (2)
Table 46: Three-phase non-directional overcurrent protection, high stage (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC2
2920 182.08 .Str.general START General start 1=Start
2921 182.09 .mcd
2922 182.10 .Str.phsA phsA start 1=Start
2923 182.11 .mcd
2924 182.12 .Str.phsB phsB start 1=Start
2925 182.13 .mcd
2926 182.14 .Str.phsC phsC start 1=Start
2927 182.15 .mcd
2928 183.00 .Op.general OPERATE General operate 1=Operate
2929 183.01 .mcd
Section 2 1MRS756878 H
Modbus data mappings
32 RET615
Point List Manual