2.3.1.14  LD0.ARCSARC1 Arc protection (1)
Table 17: LD0.ARCSARC1 Arc protection (1)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.ARCSARC11      
2978 186.02 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2979 186.03 .mcd      
    LD0.ARCPTRC11      
2982 186.06 .Op.general OPERATE Stage operate 1=Operate
2983 186.07 .mcd      
2.3.1.15  LD0.ARCSARC2 Arc protection (2)
Table 18: LD0.ARCSARC2 Arc protection (2)
BitA RegA IEC 61850 name SA name Description Values
    LD0.ARCSARC21      
2984 186.08 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2985 186.09 .mcd      
    LD0.ARCPTRC21      
2988 186.12 .Op.general OPERATE Stage operate 1=Operate
2989 186.13 .mcd      
2.3.1.16  LD0.ARCSARC3 Arc protection (3)
Table 19: LD0.ARCSARC3 Arc protection (3)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.ARCSARC31      
2990 186.14 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2991 186.15 .mcd      
    LD0.ARCPTRC31      
2994 187.02 .Op.general OPERATE Stage operate 1=Operate
2995 187.03 .mcd      
2.3.1.17  LD0.CCBRBRF1 Circuit breaker failure protection (1)
Table 20: LD0.CCBRBRF1 Circuit breaker failure protection (1)
BitA
RegA IEC 61850 name SA name Description Values
    LD0.CCBRBRF1      
2828 176.12 .Str.general CB_FAULT_AL Timer running 1=Running
2829 176.13 .mcd      
Table continues on next page
Section 2 1MRS756878 H
Modbus data mappings
22 RET615
Point List Manual