Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 125
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
DCBusVoltage
This parameter provides the present DC
bus voltage level.
Parameter Number 5
Access Rule GET
Data Type UINT
Group Basic Status
Units V DC
Minimum Value 0
Maximum Value 1200
Default Value 0
Starter Status
This parameter provides the status
of the starter.
Parameter Number 6
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value OxDFFF
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X TripPresent
—————————————— X WarningPresent
————————————— X —— RunningForward
———————————— X ——— RunningReverse
—————————— X ———— Ready
—————————— X ————— NetControlStatus
————————— X —————— NetRefStatus
———————— X ——————— AtReference
——————— X ———————— DLXEnabled
—————— X ———————— KeyPadAuto
————— X —————————— KeyPadOff
———— X ——————————— KeyPadHand
——— X ———————————— KeyPadJogging
—— X ————————————— Reserved
X —————————————— DisconnectClosed
X ——————————————— BrakeStatus