Rockwell Automation Publication 1756-RM003N-EN-P - October 2011 177
Input/Output Instructions (MSG, GSV, SSV, IOT) Chapter 4
Reset electronic fuses on a digital output
module
Message Type CIP Generic
Service Type Reset Electronic Fuse
Source tag name of type DINT
This tag represents a bit mask of the points to reset fuses on.
Destination Leave blank
Reset latched diagnostics on a digital input
module
Message Type CIP Generic
Service Type Reset Latched Diagnostics (I)
Source tag_name of type DINT
This tag represents a bit mask of the points to reset diagnostics on.
Reset latched diagnostics on a digital output
module
Message Type CIP Generic
Service Type Reset Latched Diagnostics (O)
Source tag_name of type DINT
This tag represents a bit mask of the points to reset diagnostics on.
Unlatch the alarm of an analog input module Message Type CIP Generic
Service Type Select which alarm that you want to unlatch.
· Unlatch All Alarms (I)
· Unlatch Analog High Alarm (I)
· Unlatch Analog High High Alarm (I)
· Unlatch Analog Low Alarm (I)
· Unlatch Analog Low Low Alarm (I)
· Unlatch Rate Alarm (I)
Instance Channel of the alarm that you want to unlatch
Unlatch the alarm of an analog output
module
Message Type CIP Generic
Service Type Select which alarm that you want to unlatch.
· Unlatch All Alarms (O)
· Unlatch High Alarm (O)
· Unlatch Low Alarm (O)
· Unlatch Ramp Alarm (O)
Instance Channel of the alarm that you want to unlatch
If you want to In this property Type or select