46 Rockwell Automation Publication 1756-RM003N-EN-P - October 2011
Chapter 1 FactoryTalk Alarms and Events Logix-based Instructions (ALMD, ALMA)
ProgAck BOOL Set by the user program to acknowledge the alarm. Requires a cleared-to-set transition while the alarm
is unacknowledged.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
OperAck BOOL Set by the operator interface to acknowledge the alarm. Requires a cleared-to-set transition while the
alarm is unacknowledged. The instruction clears this parameter.
Default is cleared.
ProgReset BOOL Set by the user program to reset the alarm. Requires a cleared-to-set transition while the alarm is
InAlarm and the In condition is not in alarm.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
OperReset BOOL Set by the operator interface to reset the alarm. Requires a cleared-to-set transition while the alarm is
InAlarm and the In condition is not in alarm. The alarm instruction clears this parameter.
Default is cleared.
ProgSuppress BOOL Set by the user program to suppress the alarm.
Default is cleared.
OperSuppress BOOL Set by the operator interface to suppress the alarm. The alarm instruction clears this parameter.
Default is cleared.
ProgUnsuppress BOOL Set by the user program to unsuppress the alarm. Takes precedence over Suppress commands.
Default is cleared.
OperUnsuppress BOOL Set by the operator interface to unsuppress the alarm. Takes precedence over Suppress commands. The
alarm instruction clears this parameter.
Default is cleared.
ProgDisable BOOL Set by the user program to disable the alarm.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
OperDisable BOOL Set by the operator interface to disable the alarm. The alarm instruction clears this parameter.
Default is cleared.
ProgEnable BOOL Set by the user program to enable the alarm. Takes precedence over a Disable command.
Default is cleared.
Relay Ladder
Copied from the instruction operand.
Structured Text
Copied from the instruction operand.
OperEnable BOOL Set by the operator interface to enable the alarm. Takes precedence over Disable command. The alarm
instruction clears this parameter.
Default is cleared.
Input Parameter Data Type Description