Publication 1734-UM011A-EN-P - February 2004
1734-POINT I/O Module/RSLogix 5000 Controller Tag Reference C-25
To enter values from +128 to +255, use these conversion formulas:
Decimal Position Note:
Desired Decimal Position Value - 256 = Entered Decimal Position
Value.
Example: For a divisor of 200, 200 - 256 = -56
Gate Interval Note:
Desired Gate Interval Value - 256 = Entered Gate Interval Value.
Example: For a Gate Interval of 200, 200 - 256 = -56
Scalar Note:
Desired Scalar Value - 256 = Entered Scalar Value.
Example: For a Scalar of 128, 128 - 256 = -128
1734-VHSC24
1 Channel 15-24V DC Very High Speed Counter
1734-VHSC5
1 Channel 5V DC Very High Speed Counter
Configuration Data Data Type Default
Value
Valid Data Values
SS Output Control
SS Out 0 Force
SS Out 0 En
SS Out 0 Electronic Fuse
SS Out 0 Diagnostic Speed
SS Out 1 Force
SS Out 1 En
SS Out 1 Electronic Fuse
SS Out 1 Diagnostic Speed
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
0
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0=< 8ms Response
1=50ms Response
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0=< 8ms Response
1=50ms Response