Publication 1734-UM011A-EN-P - February 2004
4-18 Configure the 1734-AENT for Direct Connection in RSLogix 5000
9. Click OK.
At this point, your PointBus status LED should be solid green. All the
yellow triangles in your I/O configuration should be gone.
Configure the 1734-AENT
with Fixed IP Address
To configure the 1734-AENT with a fixed IP address to prevent the adapter
from ceasing to communicate with the ControlLogix controller:
1. Click on the Port Configuration tab in the 1734-AENT properties
window.
2. Click the Enable DHCP box so that there is not a check mark in the box.
3. Click the Set button.
4. Read and acknowledge the warning.
5. Click OK.
6. Click the Refresh button to verify the changes.

Table of Contents

Other manuals for Allen-Bradley Rockwell Automation 1734-AENT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Rockwell Automation 1734-AENT and is the answer not in the manual?

Allen-Bradley Rockwell Automation 1734-AENT Specifications

General IconGeneral
Model1734-AENT
CategoryNetwork Hardware
TypeEtherNet/IP Adapter
Ethernet Ports2
IP AddressingStatic or DHCP
Network AddressConfigurable via software
MountingDIN rail
Number of Ports2
Port TypeRJ45
Communication ProtocolEtherNet/IP
ManufacturerRockwell Automation
Power Supply24V DC
EnclosureOpen-style

Related product manuals