EasyManua.ls Logo

Ametek OCS 500N6 Series - 1-Phase Operation with 3-Phase Devices using IEC.control

Ametek OCS 500N6 Series
80 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AMETEK CTS OCS 500 N6 series
Manual for Operation V 5.24 80 / 80
12.5.
OCS 500N6 1-phase operating with 3-phase devices
A 3-phase OCS 500 N6 uses in single phase mode the following phases:
L1 = phase line L
N = neutral line N
PE = protected earth PE
L+N-PE coupling
For coupling L+N-PE
select L1+L2+L3+N-PE
The lines L2 and L3 are not connected in the OCS 500 N6
and therefore the pulse is coupled only to the connected
lines L and N to PE
Using software iec.control
Some standards and the DC coupling selection do not offer the coupling L+N-PE. For test this coupling precedes
the following steps:
Figure 11.1: Coupling L+N-PE with software IEC.control
Example for select coupling L+N-PE
1. DoubleClick into the area Standard Area for change to Device Area mode
2. Select Ringwave
3. Select radio button 4 Line + PE coupling. This offers the desired coupling mode
4. Select the button coupling for open the coupling selection
5. Select coupling L1+L2+L3+N-PE and deselect all other couplings
6. Press OK button
Save the setting as test file for use it later or in a link file.

Table of Contents

Related product manuals