Page 33
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
When the EWS consists of multiple EWCIEs networked together, only one EWCIE can be in control
at any one time, and the REMOTE CTRL indicator is illuminated at All EWCIE, except the EWCIE that
is in control. Refer to section 5.1.14
Each EWCIE is assigned a priority. A higher priority EWCIE can take control from a lower priority
EWCIE, by activating the MANUAL control at the higher priority EWCIE. Refer to the Programming
Manual for information on setting priorities.
5.4.5 Disabling Emergency Zones
There is a facility to disable one or more emergency zones.
When an emergency zone is disabled, the emergency zone status indication – Speech, Alert, Evac,
Fault and Test are extinguished, the audio and visual outputs are de-activated.
The individual emergency zone ALM indicator is unaffected. See section 5.1.12
The system wide ALARM indicator is unaffected. See section 5.3.8
The individual emergency zone DIS indicator is illuminated steady. See section 5.1.12
The system wide DISABLE indicator is illuminated steady. See section 5.3.7
5.4.5.1 To disable one or more emergency zones:
Activate the MENU control
Activate the ZONE control