Page 70
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
2
Menu Screen
The Access Level control displays
the current access level.
Activating the control will prompt
for a new User ID and password
see section 6.2.
If a level 3 user ID and password is
entered, the display is
updated as
below
3
Menu Screen Showing the access
level as 3.
6.14 FAD retrigger
Fire Alarm Devices (FADs) (or warning devices) are activated when the EWCIE enters the emergency warning
condition (see section 5.4.3).
If the FAD retrigger is On, and the EWS is silenced (after entering the emergency warning condition), and an
alarm is reported in another emergency zone, the FADs will be retriggered. If the FAD retrigger is Off, then the
FADs will not be retriggered.
This facility is at access level 3.
1
Menu control
2
Menu Screen
The FAD Retrigger control shows
retrigger as On.
To change the setting to Off,
activate the control
while at
access level 3.