OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
18
Date and time the controller uses when its real-time clock is invalid.
Time Synch Sensitivity
(seconds)
When the controller receives a time sync request, if the difference
between the controller's time and the time sync's time is greater than this
field's value, the controller's time is immediately changed. If the
difference is less than this field's value, the controller's time is slowly
adjusted until the time is correct.
BACnet third party
integration points
capacity, integration
points requested, and
integration points active
Shows how many third-party BACnet points the G5CE allows (capacity),
how many points are in the control program (requested), and how many
are currently active (not disabled in WebCTRL®).
For example, if the G5CE allows 1500 points, the control program has
1450 points, and you disabled 30 points in WebCTRL®, you would see:
Integration points capacity: 1500
Integration points requested: 1450
Integration points active: 1420
Modbus integration points
capacity and integration
points active
Shows how many Modbus points the G5CE allows (capacity) and how
many are currently active.
Number of poll retries
before Network Input
Microblocks indicate
failure
The maximum number of retries after the initial attempt that a Network
microblock will attempt to communicate with its target device. If
unsuccessful, the point will transition to an idle state for 30 seconds
before attempting to communicate again. Change this field only if
directed by Technical Support.
Periodic rebinding interval
If a microblock uses a wildcard in its address, this timer determines how
often the microblock will attempt to find the nearest instance of its target.
For example, if an outside air temperature address uses a wildcard, a VAV
application will look for the outside air temperature on the same network
segment or on the nearest device containing that object.
Enable only if directed by Automated Logic® Technical Support.