OptiFlex™ BACnet Integrator (part no. G5CE) Automated Logic Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/9/2022 All rights reserved.
20
Priorities
NOTE BACnet defines the following Network message priorities for
Alarms and Events.
Priority range
Network message priority
0063
Life Safety
64127
Critical Equipment
128191
Urgent
192255
Normal
Priority of Off-Normal
BACnet priority for Alarms.
Priority of Fault
BACnet priority for Fault messages.
Priority of Normal
BACnet priority for Return-to-normal messages.
Ack Required for
Off-Normal, Fault, and
Normal
Specifies whether alarms associated with this Notification Class require a
BACnet Acknowledgment for Off-Normal, Fault, or Normal alarms.
TIP You can require operator acknowledgment for an Alarm or
Return-to-normal message (stored in the WebCTRL® database). In the
WebCTRL® interface on the Alarm > Enable/Disable tab, change the
acknowledgment settings for an alarm source or an alarm category.
Recipient List
Recipients
The first row in this list is from the WebCTRL® application. Do not delete
this row. Click Add if you want other BACnet devices to receive alarms
associated with this Notification Class.
NOTE Additional entries in this table may be lost after a download.
Recipient Description
Name that appears in the Recipients table.
Recipient Type
Use Address (static binding) for either of the following:
Third-party BACnet device recipients that do not support dynamic
binding
When you want alarms to be broadcast (you must uncheck Issue
Confirmed Notifications). This use is rare.
Days and times
The days and times during which the recipient will receive alarms.
Recipient Device Object
Identifier
Type the Device Instance from SiteBuilder (or from the network
administrator for third-party devices) in the # field.
Process Identifier
Change for third-party devices that use a BACnet Process Identifier other
than 1. The WebCTRL® application processes alarms for any 32-bit
Process Identifier.
Issue Confirmed
Notifications
Select to have a device continue sending an alarm message until it
receives delivery confirmation from the recipient.
Transitions to Send
Uncheck the types of alarms you do not want the recipient to get.
Calendars
Calendars are provided in the driver for BACnet compatibility only. Instead, use the Schedules feature
in the WebCTRL® interface.