EasyManua.ls Logo

Avaya S8700 - Connect DC Power Cabinet Ground

Avaya S8700
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
109
Installing an Avaya SCC1 Media Gateway Stack
October 2002
Ground for the DC-Powered Distribution Unit
Figure notes
1 DC power cabinet
2 DC Power Distribution Unit
3 Ground Discharge Bar
4 6 AWG (#40) (4 mm2) Wire
5 GRD Connector Terminal on DC-Powered Distribution Unit
6 To Additional DC-Powered Distribution Units (if required)
Connect DC Power Cabinet Ground
1 Cut a length of 6 AWG (#40) (4 mm
2
) wire long enough to reach between the GROUND
DISCHARGE bar on the DC power cabinet and the single-point ground block on the
expansion control media gateway A (bottom media gateway in ‘‘Ground for Media
Gateway’’ on page 110).
2 At the DC power cabinet, connect the wire to the GROUND DISCHARGE bar.
3 Route the wire to expansion control media gateway A and connect to the single-point
ground block.
4 Repeat for each expansion control media gateway A in the S8700 Multi-Connect
configuration room.
j58890r1 RBP 042296