109
Installing an Avaya SCC1 Media Gateway Stack
October 2002
Ground for the DC-Powered Distribution Unit
Figure notes
1 DC power cabinet
2 DC Power Distribution Unit
3 Ground Discharge Bar
4 6 AWG (#40) (4 mm2) Wire
5 GRD Connector Terminal on DC-Powered Distribution Unit
6 To Additional DC-Powered Distribution Units (if required)
Connect DC Power Cabinet Ground
1 Cut a length of 6 AWG (#40) (4 mm
2
) wire long enough to reach between the GROUND
DISCHARGE bar on the DC power cabinet and the single-point ground block on the
expansion control media gateway A (bottom media gateway in ‘‘Ground for Media
Gateway’’ on page 110).
2 At the DC power cabinet, connect the wire to the GROUND DISCHARGE bar.
3 Route the wire to expansion control media gateway A and connect to the single-point
ground block.
4 Repeat for each expansion control media gateway A in the S8700 Multi-Connect
configuration room.
j58890r1 RBP 042296