EasyManua.ls Logo

Avaya S8700 - Connect DC Power to the Media Gateways

Avaya S8700
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88
Installing an Avaya MCC1 Media Gateway
October 2002
Power Distribution Unit (J58890CH)
Figure notes
1 Connect small battery holdover cable (or temperature sensor cable from large battery
cabinet) to J20
2 Carrier Circuit Breakers
3 Ground Terminal Block
4 Connect -48 VDC Return - 1 AWG (50 mm
2
) red cable here.
5 Connect -48 VDC - 1 AWG (50 mm
2
) black cable
6 1 AWG (50 mm
2
) 50 ft. (15.2 m) cable to large battery cabinet. For cables greater than 50
ft. (15.2 m), contact your Avaya representative.
7 Ground Terminal Block
8 To AC load center or approved single-point ground block
Connect DC Power to the Media Gateways
1 Be sure the main circuit breaker is OFF.
2 Measure and cut 2 pieces of 1 AWG (#70) (44 mm
2
) wire long enough to reach from the
DC power cabinet to the first media gateway.
3 At the DC power cabinet, connect the -48 volt DC wire to the DC OUTPUT circuit
breaker. See ‘‘Typical Power and Ground for a DC power cabinet’’ on page 82
. Connect
the -48 volt RTN (return) wire to the ground discharge bar.
4 Route the wires out of the cabinet, through the hole in the lower rear cover, and to the
first media gateway.
External Alarms
-4
8
V
D
C
R
e
tu
r
n
C
a
rr
ie
r
B
A
C
D
E
F
/G
R
e
m
o
te
Powe
r
-4
8
V
D
C
B
a
tte
r
ies
pcdf010 KLC 020599
1
2
3
4
5
6
7
8

Table of Contents