Configure the UPSs
October 2002
NOTE:
The Host Table should be empty. If not, in the following commands use a host table entry
that is currently unassigned.
11 Type HI1 198.152.254.201 and press Enter. (Sets the trap destination for this UPS 1)
12 Type TL1 3 and press Enter. (Sets the trap level for the host, All traps)
13 Type TT1 1 and press Enter. (Sets the trap type, Standard UPS MIB-defined)
14 Type HS and press Enter. Verify the table entries. (Re-displays the host table)
15 Type CF and press Enter. (Re-displays the basic administration screen)
16 Type SA and press Enter. (Saves configuration and restarts module)
17 When completed, disconnect the services laptop computer from the UPS.
18 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module
and the other end to the next available port on an Ethernet switch for Control Network A
(CNA).
19 Repeat steps 5 thru 18 for the UPS 2 SNMP module. Depending on the reliability
configuration to be installed use the following address, mask, and gateway information:
Duplex Reliability Configurations
For duplex reliability configurations use the following address and cable connection
information:
NOTE:
For duplex reliability configurations there are two servers and two UPS units. However,
there is only one control network. The following entries provide addresses on CNA for
UPS 2.
UPS IPaddress / Subnet mask = 198.152.255.238 / 255.255.255.0
Default Gateway IP address = 198.152.254.202
Host Table trap receiver IP address = 198.152.254.202
Local network administrator supplied information as required for Get and Set
community name strings.
Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the
Ethernet switch for Control Network A (CNA).
High/critical reliability configurations
For high and critical configurations use the following addresses and cable connection
information:
UPS IPaddress / Subnet mask = 198.152.255.239 / 255.255.255.0