Patch Cord/Jumper Installation and Administration
October 2002
equipment is connected to the 110-type wiring block. The wiring block is pre-wired to four
25-pair female connectors mounted on the outside rear of the cabinet.
1 Install D rings on the wall between the cable slack manager and the
terminal/connecting blocks mounted on the MDF.
2 Install a self-sticking port label on the rear of each connector on the B25A connector
cable. See ‘‘Self-Stick Label on 25-Pair Cable Connector’’ on page 156
.
3 Labels should be positioned so they will not be obscured by the cabinet connector
retainers.
4 At the rear of the Auxiliary cabinet, connect 1 end of the connector cable to the assigned
connector.
5 Route the cable down the rear of the cabinet and through the cable slack manager to the
MDF.
6 At the MDF, connect the other end of the cable to the assigned terminal/connecting block
connector.
7 Store the excess cable in the cable slack manager.
8 Repeat Steps 2 through 6 until all cables are installed.
Self-Stick Label on 25-Pair Cable Connector