EasyManua.ls Logo

Avaya S8700 - Page 79

Avaya S8700
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79
Installing an Avaya MCC1 Media Gateway
October 2002
Power Distribution Unit (J58890CH)
Figure notes
1 Connect small battery holdover cable (or temperature sensor cable from large battery
media gateway) to J20
2 Carrier Circuit Breakers
3 Ground Terminal Block
4 Connect -48 VDC Return - 1 AWG (50 mm
2
) red cable here.
5 Connect -48 VDC - 1 AWG (50 mm
2
) black cable
6 1 AWG (50 mm
2
) 50 ft. (15.2 m) cable to large battery media gateway. For cables greater
than 50 ft. (15.2 m), contact your Avaya representative.
7 Ground Terminal Block
8 To AC load center or approved single-point ground block
Temperature Sensor Cable Adapter Cables
H600-476 Adapter Cable Usage
Group 1 (G1) 24-cell customer-provided battery
Group 3 (G3) (included
with battery media
gateway)
24-cell Avaya battery
External Alarms
-4
8
V
D
C
R
e
tu
r
n
C
a
rr
ie
r
B
A
C
D
E
F
/G
R
e
m
o
te
Powe
r
-4
8
V
D
C
B
a
tte
r
ies
pcdf010 KLC 020599
1
2
3
4
5
6
7
8

Table of Contents

Other manuals for Avaya S8700

Related product manuals