EasyManua.ls Logo

Bayrol PoolManager PRO - Connection Options

Bayrol PoolManager PRO
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
The following terminal blocks are allocated to the relay switch outputs:
Relay switch output
Terminal block
Function
OUT 1
26
On / off switch
OUT 2
27
On / off switch
OUT 3
30
On / off switch
OUT 4
31 and 32
Changeover switch
c = Resting contact
b = Working contact
Each terminal block is set up as follows:
Terminal
Function
b
Working contact
c
Rest contact (for OUT 4 only)
a
Centre contact
L
F
Supply phase 230VAC for add-on functions.
Can be bridged to the centre contact if needed in
order to control 230VAC devices.
25.4.1 Connection options
HAZARD!
Permissible total current exceeded
in 230 V~ applications
For all 230 V~ switch outputs using PoolManager’s
®
internal 230 V~ supply (bridge from L
F
to centre contact
a), the total current must not exceed 4A in total.
The phase L
F
for supplying the add-on functions is
secured with 4 AT (F3 OUT).
Potential consequence:
Burning of conductor paths in PoolManager
®
Ensure that the permissible total current is never
exceeded.
If high currents are needed, then the voltage supply
has to be external.
Please also refer to the Chapter 230 V~ Power
supply.
HAZARD!
Exceeding the permissible switching current
or the permissible contact voltage
The electrical current must not exceed 4A per switch
output. The maximum permissible switching contact
voltages are 230 V~ or 30 V DC.
Potential consequence:
Burning of conductor paths in PoolManager
®
Ensure that permissible currents and permissible
voltages are never exceeded.
If applicable, secure the electrical circuits externally
in accordance with applicable stipulations.
If higher currents or voltages are needed, then an
external electrical power switch has to be used.
25.4.1.1 Control of an external system via 230V~ mains supply
A 230 V~ unit is connected between neutral conductor N (blue) and
phase L (brown) of the power supply, between which there is a voltage
of 230 V~ (AC voltage). Additionally, there is generally also a
protective earth connection (yellow/green).
Should a unit of this kind be controlled via a PoolManager’s
®
universal
switch output, then it has to be connected as follows (Example for
switch output OUT 1):
1
External system to be controlled
2
External systems 230 V~ power supply
3
Wire bridge in the terminal box from phase L
F
to centre
relay contact a
INFO
Connection of neutral conductor N and PE
The controlled external system's neutral conductor N
and protective earth PE can be connected to the N
F
and PE terminal blocks as shown in the figure.
Wire bridge in the terminal box from phase L
F
to centre relay contact a

Table of Contents

Related product manuals