ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 47
ATICS-2-63A-ISO
BMS
chan-
nel
Entry in the menu
1. Alarm/meas.values
Description Operating
message
Alarm mes-
sage
Error
11 11. Temperature Transformer tem-
perature
-- Temperature --
12 12. Fault location: -- EDS control -- (EDS start) --
* Message dependent on the parameter assignment in the „Settings menu 1: Changeover“ on p. 67 -> "System"
** Message dependent on the input parameter assignment (see „Messages for alarm on the digital input“ on p. 47)
The following different channel assignment applies to the Test settings in the "Interface/Profile" menu:
BMS
chan-
nel
Entry in the menu
1. Alarm/meas.values
Description Operating
message
Alarm mes-
sage
Error
4 4. t(1->2) Changeover period
of the last test
Changeover
period
--- ---
7 7. TEST:dd.mm.yy Next TEST due on
(date)
Date when due ---
8 8. Service:dd.mm.yy Next service due
on (date)
Date when due ---
Messages for alarm on the digital input
The following operating and alarm messages may appear depending on the settings in chapter
„Settings menu 6: Dig. input“ on p. 74
Menu
settings
Function of digital input Alarm on BMS bus BMS chan-
nel
off Digital input disabled No alarm -
M/A Enable manual mode Alarm "Manual mode" 5
Bypass Bypass enabled Alarm "Manual mode" 5
no2->1 Enable switch-back lock Operating message "Switch-back
lock"
4
1<->2 Change preferred line No alarm
TEST TEST- carry out changeover No alarm
ALARM Convert message on the digital input
into alarm on the BMS bus.
Alarm "Digital input" 8
OPL Convert message on the digital input
into alarm on the BMS bus.
Alarm, "Insulation fault, operating
theatre light"
8