4101-2 Controller Installation Handbook
3-10
CONN4
Function: power supply connections
Pin Function
+12 +12V DC input
0V Ground (DC -ve input)
Safety Earth
AUX IN + +ve auxiliary input (Auxiliary input fused via FS2 and then available
AUX IN - -ve auxiliary input as an output at CONN5. Used for lock strikes etc.)
CONN5
Function
: auxiliary power output, normally connected to aux power
connector strips.
Pin Function
AUX OUT + +ve auxiliary output (Auxiliary output fused via FS2 if power applied
AUX OUT - -ve auxiliary output to AUX IN connections. Used for lock strikes etc.)
Installing the RF module and teaching the
Controller its Distributor Code
Note: if a Controller is to be used with one or more 4322 Cotag
Reader modules, you must install the RF module and teach the
Controller its Distributor Code before installing any other modules.
You do not need to teach the Distributor Code to a Controller used
only for Swipe Card Reader modules and/or I/O modules.
1. Disconnect the power to the Controller before installing the RF
module.
2. The chassis in the Controller has six module slots. The RF
module must be plugged into the bottom slot (the one with the
smaller connector).
3. With the components on the underside, slide the module down
and locate its connector with the one on the chassis.
4. Press the module home by applying downward pressure on the
board directly over the connector on the motherboard.