EasyManua.ls Logo

Binder CB 170 - Zero-Voltage Relay Alarm Output Functionality

Binder CB 170
175 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CB (E7) 06/2018 Page 93/174
11.6 Zero-voltage relay alarm output
The chamber is equipped with a zero-voltage relay output which permits the
transmission of some alarm messages to a central monitoring system.
The connection is realized as a DIN socket (3
) on the chamber rear. A suitable DIN
plug is enclosed.
Figure 20: Pin configuration of the DIN socket (3
) on the chamber rear
ALARM
Pin 1: Pole, Pin 2: Break relay, Pin 3: Make contact
In case there is no alarm, contact 1 closes with contact 3.
Closing contact 1 with contact 2 switches the zero-voltage relay alarm output.
Maximum loading capacity of the switching contacts: 24V AC/DC 2.5A
DANGER
Electrical hazard.
Danger of death.
Damage to switching contacts and connection socket.
Do NOT exceed the maximum switching load of 24V AC/DC 2.5A.
Do NOT connect any devices with a higher loading capacity.
The zero-voltage relay alarm output switches at the following events:
Alarm message
Condition
Switching the alarm contact
---
Power failure immediately
“Temperature range
Temperature tolerance range alarm
(see chap. 11.1.2)
After configurable delay time (chap.
11.5). Factory setting: 10 minutes
“CO2 range”
CO
2
tolerance range alarm
(see chap. 11.1.2)
After configurable delay time (chap.
11.5). Factory setting: 10 minutes
“O2 range”
O
2
tolerance range alarm
(chamber with O
2
control)
(see chap. 11.1.2)
After configurable delay time (chap.
11.5). Factory setting: 10 minutes
“Humidity range”
Humidity tolerance range alarm
(chamber with active humidification)
(see chap. 11.1.2)
After configurable delay time (chap.
11.5). Factory setting: 10 minutes
“Door open”
Chamber door open alarm
(see chap. 11.1.2)
After configurable delay time (chap.
11.5). Factory setting: 1 minutes
In case of a tolerance range alarm or a door open alarm, the alarm message on the controller display
remains on during the alarm transmission via the zero-voltage relay outputs.
As soon as the cause of the alarm is identified and resolved, you can reset the alarm transmission via the
zero-voltage relay outputs together with the alarm message in the “Active alarmsmenu by pressing the
Reset alarm icon.
In case of a power failure, transmission of the alarm via zero-voltage relay outputs remains active for the
duration of the power failure. After power returns, contact 1 closes automatically with contact 3.
When using the communication software APT-COM™ 3 DataControlSystem (option, chap.
18.1) for data acquisition, the alarm messages are only recorded in the protocol.
Set the tolerance limits for limit alarms by APT-COM™ 3 separately in the APT-COM™ 3
measuring window.

Table of Contents

Related product manuals