EasyManua.ls Logo

Bosch Solution 16plus - Page 57

Bosch Solution 16plus
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-5
Bosch Security Systems 05/10 BLCC100I
Solution 16
plus
Installation Manual Input Programming
1) Press [MENU] + [3] + [1] + [1] and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK].
2) Use the up and down arrow keys to select the Zone Type
required then Press [OK] to save and exit or press [MENU] to
exit without saving.
Zone Type Zn001
01 - Burglary Delay 1
Press  0-9 OK to SAVE
0 Zone Not Used
Program the zone type as zero if the zone is not being used.
1 Burglary Delay 1
Zones programmed as Delay 1 will cause Entry Timer 1 to start when
tripped. The user must disarm the area before entry timer expires
or an alarm will occur. Zones set as Burglary Delay 1 are only active
when the area is armed. See MENU 7-2-1 — Entry Time 1 to set the
required delay time.
2 Burglary Delay 2
Zones programmed as Delay 2 will cause Entry Timer 2 to start when
tripped. The user must disarm the area before entry timer expires
or an alarm will occur. Zones set as Burglary Delay 2 are only active
when the area is armed. See MENU 7-2-2 — Entry Time 2 to set the
required delay time.
3 Burglary Instant 1
Zones programmed as Instant 1 will immediatly cause the alarm
to trigger when the zone is tripped. ie No Entry Delay. Zones set as
Burglary Instant 1 have Exit Delay and are only active when the area is
armed. See MENU 7-2-0 — Exit Time
4 Burglary Instant 2
Zones programmed as Instant 2 will immediatly cause the alarm to
trigger when the zone is triggered. ie. No Entry Delay. Zones set as
Burglary Instant 2 have NO Exit Delay and are only active when the
area is armed.
5 Burglary Handover
A Handover zone will provide a delayed alarm only when a delay zone
has been tripped rst (ie. the entry time is active) otherwise it will
trigger an instant alarm.
Zones programmed as Handover can be set to sequential or non-
sequential handover. At factory default, handover is set to sequential
which means that zone must be triggerred in numerical order for the
delay to handover. Non Sequential Handover means the zone do not
have to be programmed in numerical order. In both cases an entry
delay zone must be triggered rst for the delay to handover.
See MENU 2-1-2 — Input Options to set Non Sequential Handover.
i
Note
The Zone Types listed above will only trigger an alarm if the
system or area is in the armed state and the exit time has exprired.
Zones must be sealled at the end of exit time to trigger alarms.
6 Burglary 24-Hour
Zones programmed as 24-hour burglary will trigger an alarm as soon
as the zone becomes faulted regardless of what state the area is in.
24-Hour zones are active 24 hours a day. A 24hr Burglary report will
be sent to the central station receiver.
7 Tamper 24-Hour
Zones programmed as 24-Hour Tamper will trigger an alarm as soon
as the zone becomes faulted regardless of what state the area is in.
24-Hour zones are active 24 hours a day. A 24hr Tamper report will be
sent to the central station receiver.
8 Hold Up 24-Hour
Zones programmed as 24-Hour Hold Up will trigger a Silent alarm as
soon as the zone becomes faulted regardless of what state the area
is in. 24-Hour zones are active 24 hours a day. A 24hr Hold Up report
will be sent to the central station receiver. No Siren/Strobe or Keypad
indication will be given. To view the status of a 24hr hold up zone,
refer to MENU 3-0-1.
i
Note
In software versions earlier than 1.07 the keypad would display
the status of 24hr hold up zones via the status line. To rectify this
please upgrade the panel rmware.
9 Medical 24-Hour
This zone type is used for personal medical emergency alarms. Zones
programmed as 24-Medical will trigger an alarm as soon as the zone
becomes faulted regardless of what state the area is in. A 24hr Medical
report will be sent to the central station receiver.
10 Panic 24-Hour
This zone type is used for a general type of emergency including the
presence of one or more unwanted persons trying to gain entry to
the premises. It will sound an alarm at any time as soon as the zone
becomes faulted regardless of what state the area is in. A 24hr Panic
report will be sent to the central station receiver.
11 Fire 24-Hour
This zone type is used for Fire and Smoke detector alarms. Zones
programmed as 24hr Fire will trigger an alarm as soon as the zone
becomes faulted regardless of what state the area is in. A 24hr Fire
report will be sent to the central station receiver.
If a horn speaker is connected and programmed, a distinct re sound
will be heard to indicate that it is a re alarm that has registered. The
re sound via the horn speaker is dierent than the burglary sound.
13 Keyswitch
A keyswitch zone can be used as an input terminal to turn on and/or
o an area. Refer to MENU 3-4-1 — Keyswitch Options to select the
various options such as latching or momentary arm and/or disarm etc.
When reporting back to base, the keyswitch user number will follow
the actual zone number.
14 – Display Only
A display zone is not a burglary zone. It can never sound the sirens or
trigger the dialler. Its purpose is to only display on the keypad when
faulted.
15 24-Hour Non Burglary
This zone type operates as a 24-hour type and is used for non-specic
alarms such as water level or temperature sensors.
i
Note
The 24 Hour Zone Types listed above are active 24hrs a day. They
will trigger an alarm regardless of whether or not the system or
area is in the Armed, Part Armed or Disarmed state.

Table of Contents

Other manuals for Bosch Solution 16plus

Related product manuals