7-6
Bosch Security Systems 05/10 BLCC100I
Solution 16
plus
Installation Manual Input Programming
Inputs > Zone Properties >
Area Assignment
MENU 3-1-2
1
This menu programs which area or partition each zone belongs
to. The system can be partitioned to a maximum of 4 separate
areas. Each zone can only be assigned to a single area. For
installations requiring a common access point, it is possible
to set Area 1 to be a common area. See MENU 7-7-1 — Area
Options
1) Press [MENU] + [3] + [1] + [2] and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK].
Area Assignment Zn001
01 - Area 1
Press 0-9 OK to SAVE
2) Use the up and down arrows to select the area that you want to
assign the zone to.
3) Press [OK] to save and exit or press [MENU] to exit without
saving.
Inputs > Zone Properties >
Pulse Count
MENU 3-1-3
0 0
PULSES
Pulse Count sets the number of trigger pulses a single zone
must receive before an alarm will be tripped. The number of
pulses must be detected within the Pulse Count Time period for
an alarm to occur. See MENU 3-1-4 — Pulse Count Time
A feature called Pulse Count Handover can be enabled allowing
pulses registered by one zone to handover to another zone
provided they are the same Zone Type (ie. instant zone to instant
zone) and in the same Area. See MENU 2-1-2 — Input Options
When pulse count hands over from one zone to another and an
alarm is triggered, a cross alarm report will be sent to the central
station.
1) Press [MENU] + [3] + [1] + [3]and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK]. The
keypad will display the current pulse count time for the chosen
zone.
Pulse Count Zn001
00
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the number of pulses required.
Valid entries are 0 – 15 pulses.
3) Press [OK] to save and exit or press [MENU] to exit without
saving.
Inputs > Zone Properties >
Pulse Count Time
MENU 3-1-4
1 2 0
SECONDS
This menu sets the time period during which the number of
zone trigger pulses must be received for an alarm to occur. The
zone must be set as a Pulse Count Zone for this time to have
any eect.
1) Press [MENU] + [3] + [1] + [4] and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK]. The
keypad will display the current pulse count time.
Pulse Count Time Zn001
120 Seconds
Press 0-9 OK or MENU
2) Using the numeric keys, enter the required Pulse Count Time.
Valid entries are 0 – 255 seconds.
3) Press [OK] to save and exit or press [MENU] to exit without
saving.
UND ERS TA ND I NG ACC ES S G R OUP S
Access Groups are used to link Readers, Users and Outputs
together to allow you to operate a door strike when a user token
is presented to a given reader. To do this you need to create an
access group and assign the user, the reader and the output to
the same access group.
Users
A user can belong to multiple Access Groups.
Outputs
An output can only belong to 1 Access Group.
Reader
A reader can belong to only 1 Access Group.
Access Group
There are 8 dierent access groups.
Door Access Group Example
1) To set up a door access group you need to select an unused
Access Group number from 1 to 8, in this example we will
assume the Access Group number to be 5.
2) Under user properties assign the users who you wish to have
access to Access Group 5. Remember that you are able to
assign users to more than one Access Group.
3) Now select the output that will be used to operate the door
strike and assign it to Access Group 5. You also need to set the
output type to ACCESS and the polarity to one shot low with a
time of how long you would like the strike to operate.
Generally a strike would be operated for 5 seconds.
4) Assign the Reader under Reader properties to Access Group 5.