Chapter 6 - Parameter Description
6-22
)5+" " ">"@
FG2-92 allows loading all previously saved VFD
parameters from keypad to VFD memory. When
VFD is at stop mode and FG2-92is set to Yes, the
VFD parameters will be loaded from Keypad to
VFD memory. One keypad can be used to load the
same set of parameters to multiple VFDs with
different HP ratings. When loading process is done,
the display will show No again. Loading of
parameters from keypad to VFD is possible only
with identical software versions.
)5.+$! C" "
FG2-93 allows different modes of resetting the
VFD parameters to default settings. There are eight
selections: All Groups, DRV, FG1, FG2, I/O, APP,
COM, and EXT. In order to reset all VFD
parameters to default settings, the All Groups
option should be selected. For example, if multiple
parameters were changed in I/O group and they
need to be set to default settings again, select I/O
group in FG2-92 to reset only this group. When
reset process is done, the display will show No.
)5/+""" "  !<9=
FG2-94 is used to lock the parameters from being
changed. When the parameters are locked, the
display arrow changes from solid to triangle.
The lock and unlock code is 12.
)57+""& "
FG2-95 should be used every time a parameter
setting is changed. Some parameters can lose their
new value at VFD power cycling if they were not
saved with FG2-91or FG2-95.
FG2
Para. Write
92 No
FG2
Para. Init
93 No
FG2
Para. Lock
94 0
FG2
Para. Save
95 No