Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-11
Chapter 12 Cisco ASR 1001 Router Overview and Installation
Cisco ASR 1001 Router Power Supply Installation
Figure 12-30 shows the DC power supply with lead wires.
Figure 12-30 DC Power Supply with Lead Wires
Step 7 Insert the exposed wire of one of the ground wire into the terminal block plug. Ensure that you cannot
see any wire lead. Only wires with insulation should extend from the terminal block.
Caution Do not overtorque the terminal block plug captive screws. The recommended maximum torque is from
0.5 Nm (4.425 lbf in.) to 0.6 Nm (5.310 lbf in.).
1 Negative (–) lead wire 3 Ground lead wire
2 Positive (+) lead wire
207765
1
2
3