Chapter 12      Cisco ASR 1001 Router Overview and Installation
Cisco ASR 1001 Router Power Supply Installation
Step 8 Use a ratcheting torque screwdriver to torque the terminal block plug captive screw (above the installed 
wire lead) to from 0.5 Nm (4.425 lbf in. to 0.6 Nm (5.310 lbf in.), as shown in Figure 12-31.
Figure 12-31 Torquing the DC Power Supply Terminal Block Plug Screws
Step 9 Repeat Step 6 through Step 8 for the remaining two DC input power source wires, the positive lead wire 
and the negative lead wire.
Figure 12-32 shows how to insert the DC power supply terminal block plug in the block header.
Figure 12-32 Inserting the DC Power Supply Terminal Block Plug in the Block Header
1 Torque is from 0.5 Nm (4.425 lbf in.) to 0.6 Nm (5.310 lbf in.)
1 DC power supply negative (-) lead wire 3 DC power supply ground lead wire
2 DC power supply positive (+) lead wire — —