InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
This setpoint is used to adjust the load reserve for stop in relative mode. i.e.
Pwr mgmt mode = REL (%) if the reserve set #4 is active. Learn more about
reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for
start.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.22 Setpoint: #NextStrt Del
This setpoint is used to adjust the delay of starting the next gen-set when the
actual load reserve drops below the adjusted reserve for start, but the group
is still not overloaded.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.23 Setpoint: #OverldNext Del
If the system reserve drops below the start limit for next gen-set the delay
#NextStrt del will begin to count down. But if the load raises too quickly it
might happen that the system gets overloaded already before the delay
#NextStrt del reaches zero.