Page 18
Option Keypad Medical to Output - This option is used to send the manual Keypad Medical alarm function
to an output. The keypad Medical alarm is generated when a user presses buttons 7 & 9
Simultaneously at the keypad.
Option Cabinet Tamper to Output - This option is used to send activations of the common Tamper Input to
an output. This common tamper input is normally used to Monitor the panel cabinet and satellite
tamper switches.
Option Duress Alarm to Output - This option will send the Duress Function to an output. Programming of
the Duress Digit is at address 230.
Option Mails Fail To Output - A mains failure will be indicated at this output when option 7 is enabled at this
address. The Alarm Reset Timer must be set to “0” when this option is used.
Option Low Battery - A battery Low condition will be indicated at this output when option 8 is enabled at this
address. The alarm reset timer must be set to “0” when this option is used.
Address 42 - 48 as per 41 above for Outputs 2-8
‘Armed’ Zone Alarms to Outputs
When a zone is in alarm (during the ARMED state only) this block of addresses allows individual zones to be sent
to selected outputs. The default setting is that zones 1-8 will turn on all outputs 1-8 when in alarm.
51 Zone Alarms to Output #1. Options=Zones 1-8 (Default=1-8)
52 Zone Alarms to Output #2. Options=Zones 1-8 (Default=1-8)
53 Zone Alarms to Output #3. Options=Zones 1-8 (Default=1-8)
54 Zone Alarms to Output #4. Options=Zones 1-8 (Default=1-8)
55 Zone Alarms to Output #5. Options=Zones 1-8 (Default=1-8)
56 Zone Alarms to Output #6. Options=Zones 1-8 (Default=1-8)
57 Zone Alarms to Output #7. Options=Zones 1-8 (Default=1-8)
58 Zone Alarms to Output #8. Options=Zones 1-8 (Default=1-8)
‘STAY’ Mode Zone Alarms to Outputs
When a Stay Mode zone is in alarm (during the Stay state only) this block of addresses allows individual zones to
be mapped to selected outputs. The default setting is that zones 1-8 will turn on output 2 only when a Stay mode
alarm occurs.
61 Stay Mode Zone Alarms to Output #1. Options=Zones 1-8 (Default=None)
62 Stay Mode Zone Alarms to Output #2. Options=Zones 1-8 (Default=1-8)
63 Stay Mode Zone Alarms to Output #3. Options=Zones 1-8 (Default=None)
64 Stay Mode Zone Alarms to Output #4. Options=Zones 1-8 (Default=None)
65 Stay Mode Zone Alarms to Output #5. Options=Zones 1-8 (Default=None)
66 Stay Mode Zone Alarms to Output #6. Options=Zones 1-8 (Default=None)
67 Stay Mode Zone Alarms to Output #7. Options=Zones 1-8 (Default=None)
68 Stay Mode Zone Alarms to Output #8. Options=Zones 1-8 (Default=None)
‘24 HOUR’ Zone Alarms to Outputs
When a 24 Hour zone is in alarm this block of addresses allows individual zones to be sent to selected outputs.
The default setting is that zones 1-8 will turn on output 2 only when a 24 Hour alarm occurs.
71 24 Hour Zone Alarms to Output #1. Options=Zones 1-8 (Default=None)
72 24 Hour Zone Alarms to Output #2. Options=Zones 1-8 (Default=1-8)
73 24 Hour Zone Alarms to Output #3. Options=Zones 1-8 (Default=None)
74 24 Hour Zone Alarms to Output #4. Options=Zones 1-8 (Default=None)