Page 37
Contact ID Code - Panic
This address (329) is used to set the Contact ID code that a Keypad “Panic” or “1&3” alarm will transmit.
329 Keypad Panic Alarm Contact ID Code - 3 Digit Number (Default = 120)
Contact ID Code - Fire
This address (330) is used to set the Contact ID code that a Keypad Fire “4&6” alarm will transmit.
330 Keypad Fire Alarm Contact ID Code - 3 Digit Number (Default = 110)
Contact ID Code-Medical
This address (331) is used to set the Contact ID code that a Keypad Medical “7&9” alarm will transmit.
331 Keypad Medical Alarm Contact ID Code - 3 Digit Number (Default = 100)
Commonly Used Contact ID Codes
130 = Burglary 115 = Manual Call Point
131 = Perimeter Zone 122 = Silent Panic
133 = 24 Hour Zone 123 = Audible Panic
120 = Panic 159 = Low Temperature159 = Low Temperature
110 = Fire Alarm 152 = Refrigeration Alarm
111 = Smoke Detector 154 = Water Leakage
114 = Heat Detector 151 = Gas Detector
100 = Medical 116 = Duct Detector
101 = Medical Pendant
Account Numbers
The account code is the 4 digit number that identifies the panel to the Central Station. If send Group numbers is set
for Contact ID then the account number used is Partition “A”. (The special characters B,C,D,E & F can be entered at
these addresses if required (see the table on page 38 for instructions).
506 Account Code For Partition “A” - Value = 4 character code (Default = 0000)
507 Account Code For Partition “B” - Value = 4 character code (Default = 0000)
Listen-in Options - Keypad
The panel provides the facilities to use the buzzer in the keypad as a speaker to listen to the call being made by the
dialler. To use this feature a 5th wire must be connected between the panel and a keypad using the listen-in
terminals.
189 Œ Listen-in Enabled when dialling only and in Disarmed State - Default on
• Listen-in Enabled when dialling only and in Armed State - Default on
Ž Listen-in Enabled when dialling only and in Stay Mode - Default on
• Listen-in Enabled through the entire call only in Disarmed state - Default on
• Listen-in Enabled through the entire call only in Armed State - Default on
‘ Listen-in Enabled through the entire call only in Stay Mode - Default on
’ Listen-in Enabled when the panel answers a call - Default on
“ Listen-in on at All Times - Default off