Page 19
75 24 Hour Zone Alarms to Output #5. Options=Zones 1-8 (Default=None)
76 24 Hour Zone Alarms to Output #6. Options=Zones 1-8 (Default=None)
77 24 Hour Zone Alarms to Output #7. Options=Zones 1-8 (Default=None)
78 24 Hour Zone Alarms to Output #8. Options=Zones 1-8 (Default=None)
‘CHIME’ Zones to Outputs
When a Chime zone is unsealed this block of addresses allows individual zones to be sent to selected outputs.
The default setting is that no Chime zones are sent to any of the 8 outputs.
81 Chime Zone to Output #1. Options=Zones 1-8 (Default=None)
82 Chime Zone to Output #2. Options=Zones 1-8 (Default=None)
83 Chime Zone to Output #3. Options=Zones 1-8 (Default=None)
84 Chime Zone to Output #4. Options=Zones 1-8 (Default=None)
85 Chime Zone to Output #5. Options=Zones 1-8 (Default=None)
86 Chime Zone to Output #6. Options=Zones 1-8 (Default=None)
87 Chime Zone to Output #7. Options=Zones 1-8 (Default=None)
88 Chime Zone to Output #8. Options=Zones 1-8 (Default=None)
Zone Tampers to Outputs
When a zone input is set for Dual-End-of-Line (Address 130) the short & open circuit tampers are automatically
enabled for that zone input. This option allows the zone tamper alarms to be mapped through to individual
outputs. A zone tamper 1-4 is a short on the input and a zone tamper 5-8 is an open loop.
91 Zone Tamper to Output #1. Options= Zone Tampers 1-8 (Default=1-8)
92 Zone Tamper to Output #2. Options= Zone Tampers 1-8 (Default=1-8)
93 Zone Tamper to Output #3. Options= Zone Tampers 1-8 (Default=1-8)
94 Zone Tamper to Output #4. Options= Zone Tampers 1-8 (Default=1-8)
95 Zone Tamper to Output #5. Options= Zone Tampers 1-8 (Default=1-8)
96 Zone Tamper to Output #6. Options= Zone Tampers 1-8 (Default=1-8)
97 Zone Tamper to Output #7. Options= Zone Tampers 1-8 (Default=1-8)
98 Zone Tamper to Output #8. Options= Zone Tampers 1-8 (Default=1-8)
Remote Control Buttons to Outputs
When a Remote Control Button is to be used to operate a garage door or similar function this block of addresses
allows individual Buttons to be sent to selected outputs. The default setting is that none of the 8 Buttons are sent
to any outputs.
101 Buttons to Output #1. Options=Buttons 1-8 (Default=None)
102 Buttons to Output #2. Options=Buttons 1-8 (Default=None)
103 Buttons to Output #3. Options=Buttons 1-8 (Default=None)
104 Buttons to Output #4. Options=Buttons 1-8 (Default=None)
105 Buttons to Output #5. Options=Buttons 1-8 (Default=None)
106 Buttons to Output #6. Options=Buttons 1-8 (Default=None)
107 Buttons to Output #7. Options=Buttons 1-8 (Default=None)
108 Buttons to Output #8. Options=Buttons 1-8 (Default=None)
Temporary Output Disable
This Address 109 allows a technician to select any output/s to be temporarily disabled for one alarm or armed
cycle, eg by turning on LEDS 1-4 at 109 then leaving program mode, outputs 1-4 will not turn on following any
alarms. The technician is now free to arm the system to test all Staying signals without having all of the internal &
external alarms activating. When the alarm is reset or disarmed all outputs will now work normally again.
109 Select output # 1-8