Page 27
Zone Doubling & EOL OptionsZone Doubling & EOL Options
130 Single Zone EOL or dual zone input - This option is used to define the Power Wave-8 as a 4 zone
panel with or without EOL (End of Line Resistors) or an 8 zone panel. Options 1-4 relate to zones 1-4
respectively and decide whether the zone input requires an end of line resistor or just a short or open
circuit to seal the zone. If the LED’s are OFF (Type 1 Drawing on Page 5) then a short on the input is all
that is needed to seal the input. If the LED’s 1-4 are ON (Type 2 Drawing on Page 5 ) then the input
requires a 2k2 resistor to seal the zone. Options 5-8 relate to zone inputs 1-4 respectively and allow
“Zone Doubling” to be turned on for a particular input. When a zone has been assigned "Zone Doubling"
the one input is used for both a low (1-4) and a high (5-8) zone. When zone doubling is turned On, zone
1 input is used for zones 1 & 5, zone 2 input is used for zones 2 & 6, zones 3 input is used for zones 3 &
7 and zone 4 input is used for zones 4 & 8. Zone doubling is assigned on a zone-by-zone basis. Each
input can be configured as two zones (Type 3 drawing on page 5 ) without tamper monitoring or two
zones (Type 4 drawing on page 5) with tamper monitoring. To use the Type 3 mode for zones 1 & 5 you
must turn LED#1 Off and LED#5 On. To use Type 4 mode for zones 1 & 5 you must turn LED#1 On and
LED#5 On. The same applies to the other zone inputs. Refer to the table on Page 5 for more details.
Default =1-4 On
Zone Inactivity Timer
240 Inactivity Timer - 0-255 Hours. Default =120 Hours
Entry Delays
301 Zone 1 Entry Delay Time - 0-9999 Seconds (Default = 20 Sec)
302 Zone 2 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
303 Zone 3 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
304 Zone 4 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
305 Zone 5 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
306 Zone 6 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
307 Zone 7 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
308 Zone 8 Entry Delay Time - 0-9999 Seconds (Default = 0 Sec)
Exit Delays
219 Partition “A” Exit Delay Time - 0-255 Seconds (Default = 20 Sec)
220 Partition “B” Exit Delay Time - 0-255 Seconds (Default = 20 Sec)
Pulse Count Timer
229 Pulse Count Timer - 0-255 Seconds (Default = 60 Sec)