140 24 Hour Zones Zones 1-8. (Default = No zones)
Only zones programmed at this address will be active at all times. If a 24 hour zone has an entry delay
assigned to it, the entry delay acts as an abort timer e.g. the zone must be in alarm longer than the entry
delay time before the alarm is activated. If the zone is sealed before the entry delay expires, no alarm is
generated.
141 Non-Latching 24 Hour Zone Zones 1-8. (Default = No zones)
A Non-Latching 24 Hour Zone will operate as a normal 24 Hour zone except that when the zone re-seals
the zone LED and any assigned outputs will reset automatically.
142 Swinger Shutdown (1 Shot Siren Lockout) Zones Zones 1-8. (Default = No zones)
A Lockout Zone will only cause the alarm output to sound once during and armed period. If the lockout
function is not programmed then the zone can cause the audible alarms to sound on every zone alarm. In
the case of a 24 hour zone, if this option is turned on then the zone will only activate the alarm output/s
once and must be reset by a code before another alarm signal can operate the output/s again.
143 Chime (Day) Zone when Disarmed Zones 1-8. (Default = No zones)
A Chime Zone can be used as a door minder in a shop to warn when a customer has entered the premises.
A Chime zone works when the alarm is disarmed, but becomes a normal security zone when armed. Chime
zones can be temporarily disabled with the “Control” button if programmed to do so.
144 Permanent Chime (Day) Zone Zones 1-8. (Default = No zones)
A Permanent Day Zone can be used as a door minder in a shop to warn when a customer has entered the
premises. A Permanent Chime zone will never cause an activation when the alarm is armed). Chime zones
can be temporarily disabled with the “Control” button if programmed to do so.
145 Force Arm Zones Zones 1-8. (Default = No zones)
This option allows programming of which zones can be unsealed and still allow the panel to arm. Option 4
at Address 170 must be on before this address has any effect. This option allows setting (Arming) of the
panel if low security areas are not sealed at the time of arming.
146 Report Excluded Zones to Monitoring Station Zones 1-8. (Default = All zones)
If this option is on then the zone will report any exclusion (Bypass) of the zone to a Staying Station via
Contact ID or 4 + 2.
147 Send Multiple Alarms to Monitoring Station Zones 1-8. (Default = All zones)
If this option is assigned to the zone, the zone can send multiple activation reports to a Staying company
during any armed cycle. If off, the zone can only send one activation per armed cycle. In the case of a 24
hour zone, if this option is turned off then the zone will only send one signal via the dialler and must be reset
by a code before another signal can be sent.
148 Report Zone Tampers to Monitoring Station Zones 1-8. (Default = All zones)
This option allows the programming of zone tampers to be sent via the dialler to a Staying Station.
149 Common Zone Reports Area “B” Account Zones 1-8. (Default = All zones)
When a zone is in both partitions A&B this address allows the option of specifying which account number a
zone alarm will report to. The default is that a common zone will report to area A account code (Address
332) but if this option is on for a common zone it will report to area B account code (Address 333).
150 Zone Inactivity Timer Zones 1-8. (Default = None)
This option allows the programming of which zones will be Stayed for inactivity. All zones programmed
with this feature ON will be Stayed for activity for the period set below (Address 240). The inactivity timer
only works during the disarmed state and is accumulative, which means that if a zone does not trip at least
once during a disarm period the inactivity timer is not reset for that zone and will continue with the balance
of the time period left when the panel is next disarmed. The timer for each zone is reset every time a
zone unseals.