EasyManua.ls Logo

Danfoss TTS300

Danfoss TTS300
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.22 Inverter
ThefunctionoftheInverteristotaketheDCbusvoltageasaninputandgeneratetheACoutputvoltagetothe
compressormotorattherequiredfundamentalfrequencytogeneratetherequestedshaftspeed.Voltagetothe
motorisalsocontrolledtoprovidetheappropriatemotortorque.
TheBackplanesends+24VDCandgatingsignalstotheInverterfromtheBMCC.Inreturn,theInvertersendscurrent,
temperature,error,andDCbusvoltageinformationtotheBMCCviatheBackplane.Motorcurrentsandvoltages
displayedintheSMTcannotbedirectlycomparedorcorrelatedtoincoming3-phaseACvalues.
Intheeventofa3-phasevoltagepowerlosswhilethecompressorisrunning,theInverterswitchestoGenerator
Mode,actingasarectifiertomaintaintheDCbusvoltageuntiltheshaftcomestoacompletestopandde-levitates.
4.22.1 Inverter Connections
Figure 4-189 Inverter Connections
4.22.2 Inverter Verification
ThisprocedureonlyverifiestheInverterhigh-powerdiodes.TheInverterControlBoardcannotbeverifiedinthe
fieldunlessaninvertertesterisused.AfaultyInvertermayalsoappearasan“InverterError”fault.
1. IsolatethecompressorpowerasdescribedinSection1.8ElectricalIsolationonpage22.
2. RemovetheSoftStartModule.RefertoSection4.14.3SoftStartRemovalandInstallationonpage117.
3. RemovetheDCCapacitorBusBarAssembly.RefertoSection4.21.3DCCapacitorBusBarAssembly
RemovalandInstallationonpage168.
4. RemovetheCopperTubesandfastenersconnectingthemotorbusbarstotheInverterModule.Refer
toFigure4-195InverterCopperTubeRemovalonpage180.
5. DisconnecttheInverterribboncablefromtheInverterModule.
CAUTION
AfaultyInvertermodulecouldbetheresultofafaultyStator.IfanInvertermoduleisfoundtobefaulty,theStatormustbeverifiedas
well.
6. Usingamultimetersetfordiodemeasurements,placethered(+)multimeterleadonthephase1AC
terminalandtheblack(-)multimeterleadontheDC+terminal.Themeasuredvalueshouldbe0.275V
0.4V.RefertoFigure4-190InverterDiodeMeasurements(Skiip613Shown)onpage177forthisand
Page 176 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss TTS300

Related product manuals