Table 5-3 Compressor Status 2 Faults
Compressor Status 2 Fault Description
SuctionPressureSensorFault
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadablerange
andindicatesanerrorinthereading,orafunctionalproblemwiththesensor.-onlyavailablein4.X
SuctionTemperatureSensor
Fault
DischargePressureSensorFault
DischargeTemperatureSensor
Fault
InverterTemperatureSensor
Fault
CavityTemperatureSensorFault
SoftStartTemperatureSensor
Fault
InvalidBearingCalibrationFault AvalidbearingcalibrationisnotstoredintheEEPROM.
InverterCoolingControlFault ThemeasuredInverterTemperaturehasexceededtheCoolingControlFaultlimitaftertheFaultDelaytimerhas
expired.Ifthetemperaturerisesabovethefaultlimit,thefaultdelaytimerwillbegin,ifthetemperaturefalls
belowthefaultlimit,thetimerwillbereset,thecompressorwillstopifthetimerexpires.
MotorCoolingControlFault ThemeasuredCavityTemperaturehasexceededtheCoolingControlFaultlimitaftertheFaultDelaytimerhas
expired.Ifthetemperaturerisesabovethefaultlimit,thefaultdelaytimerwillbegin,ifthetemperaturefalls
belowthefaultlimit,thetimerwillbereset,thecompressorwillstopifthetimerexpires.
Table 5-4 Motor Fault Types
Motor/System Status Description
MotorSinglePhaseOvercurrent
Fault
Measuredpeakcurrentvalueofanysinglephasetomotor(fromInverter)exceedsthefaultlimit.
DCBusOvervoltageFault ThemeasuredDCbusvoltagehasexceededtheMaximumDCBusVoltagelimit,whileRPMis>0
MotorHighCurrentFault ThemotorcurrenthasexceededMaximumMotorCurrentlimit.
InverterError Inverterreportsagenericerror,orcommunicationtoBMCCislost.
BearingFaultActive IfaBearingStatusFaulttypeispresent,thentheBearingFaultActiveistriggered.Thisisnotanactualfault,only
anindicationthatafaulthasoccurredintheBearingStatussection.
RotorStartingTorqueFault MotorCurrentmaximumhasbeenexceededduringcompressorstart-up.
LowInverterCurrentFault Measuredcurrenttomotor(fromInverter)hasnotreachedtheMinimumPowerlimit.
DCBusUnder/OverVoltage
Fault
At0RPM:ThemeasuredDCBusvoltageismeasuredlowerorhigherthantheDCBusUnderorOverVoltageFault
limits.
24VDCUnder/OverVoltage
Fault
Themeasured24VDCsupplyisoutsidetherangeoftheloworhighlimit.
LowMotorBackEMFFault ThecalculatedmotorbackEMFhasfallenbelowtheminimumBackEMFlimit.
EEPROMChecksumFault Anerror(checksumerror)occursreadingthedatatablefromtheEEPROM.
GeneratorModeActive Atgreaterthan0RPMandDCbusvoltagelow,Generatormodeisenabled,switchingtheInvertertorectifier
functiontomaintaintheDCbusvoltageuntiltheshaftcomestoastopanddelevitates.
SCRRippleVoltageFault TheDCbusvoltagerippleexceedstheSCRVoltageRippleFaultlimit.
SysteminStartupmode Thecompressorinitializationhasnotfinished.Pleasewait.Compressorisresettingafterapowercycle.Thisisa
statusmessage.
M-SV-001-EN Rev. H-1/23/2023 Page 253 of 294

Table of Contents

Other manuals for Danfoss TTS300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss TTS300 and is the answer not in the manual?

Danfoss TTS300 Specifications

General IconGeneral
BrandDanfoss
ModelTTS300
CategoryAir Compressor
LanguageEnglish

Related product manuals