EasyManuals Logo
Home>Danfoss>DC Drives>VLT AHF 005

Danfoss VLT AHF 005 User Manual

Danfoss VLT AHF 005
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #133 background imageLoading...
Page #133 background image
Operation
status
Description
Current
high
The drive output current is above the limit set in parameter 4-51 Warning Current High.
Current low
The drive output current is below the limit set in parameter 4-52 Warning Speed Low.
DC hold
DC hold is selected in parameter 1-80 Function at Stop and a stop command is active. The motor is held by a DC
current set in parameter 2-00 DC Hold Current.
DC stop
The motor is held with a DC current (parameter 2-01 DC Brake Current) for a specified time (parameter 2-02 DC Brak-
ing Time).
DC brake is activated in parameter 2-03 DC Brake Cut In Speed [RPM] and a stop command is active.
DC brake (inverse) is selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is not active.
The DC brake is activated via serial communication.
Feedback
high
The sum of all active feedback is above the feedback limit set in parameter 4-57 Warning Feedback High.
Feedback
low
The sum of all active feedback is below the feedback limit set in parameter 4-56 Warning Feedback Low.
Freeze out-
put
The remote reference is active, which holds the present speed.
[20] Freeze Output was selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is active. Speed control is only possible via the terminal functions speed up and speed
down.
Hold ramp is activated via serial communication.
Freeze out-
put request
A freeze output command has been given, but the motor remains stopped until a run permissive signal is re-
ceived.
Freeze ref.
[19] Freeze Reference was selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is active. The drive saves the actual reference. Changing the reference is now only possible via
terminal functions speed up and speed down.
Jog request
A jog command has been given, but the motor is stopped until a run permissive signal is received via a digital
input.
Jogging
The motor is running as programmed in parameter 3-19 Jog Speed [RPM].
[14] Jog was selected as function for a digital input (parameter group 5–1* Digital Inputs). The corresponding
terminal (for example, terminal 29) is active.
The jog function is activated via the serial communication.
The jog function was selected as a reaction for a monitoring function (for example, No signal). The monitoring
function is active.
Motor check
In parameter 1-80 Function at Stop, [2] Motor Check was selected. A stop command is active. To ensure that a motor
is connected to the drive, a permanent test current is applied to the motor.
OVC control
Overvoltage control was activated by [2] Enabled in parameter 2-17 Over-voltage Control. The connected motor is
supplying the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in
controlled mode and to prevent the drive from tripping.
Power unit
off
(For drives with a 24 V external supply installed only.) Mains supply to the drive is removed, but the control card is
supplied by the external 24 V.
Protection
md
Protection mode is active. The unit has detected a critical status (an overcurrent or overvoltage).
AQ262141314214en-000301 / 130R0880 | 133Danfoss A/S © 2021.11
Maintenance, Diagnostics, and
Troubleshooting
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals