The drive output current is above the limit set in parameter 4-51 Warning Current High.
The drive output current is below the limit set in parameter 4-52 Warning Speed Low.
DC hold is selected in parameter 1-80 Function at Stop and a stop command is active. The motor is held by a DC
current set in parameter 2-00 DC Hold Current.
The motor is held with a DC current (parameter 2-01 DC Brake Current) for a specified time (parameter 2-02 DC Brak-
ing Time).
DC brake is activated in parameter 2-03 DC Brake Cut In Speed [RPM] and a stop command is active.
DC brake (inverse) is selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is not active.
The DC brake is activated via serial communication.
The sum of all active feedback is above the feedback limit set in parameter 4-57 Warning Feedback High.
The sum of all active feedback is below the feedback limit set in parameter 4-56 Warning Feedback Low.
The remote reference is active, which holds the present speed.
[20] Freeze Output was selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is active. Speed control is only possible via the terminal functions speed up and speed
down.
Hold ramp is activated via serial communication.
A freeze output command has been given, but the motor remains stopped until a run permissive signal is re-
ceived.
[19] Freeze Reference was selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is active. The drive saves the actual reference. Changing the reference is now only possible via
terminal functions speed up and speed down.
A jog command has been given, but the motor is stopped until a run permissive signal is received via a digital
input.
The motor is running as programmed in parameter 3-19 Jog Speed [RPM].
[14] Jog was selected as function for a digital input (parameter group 5–1* Digital Inputs). The corresponding
terminal (for example, terminal 29) is active.
The jog function is activated via the serial communication.
The jog function was selected as a reaction for a monitoring function (for example, No signal). The monitoring
function is active.
In parameter 1-80 Function at Stop, [2] Motor Check was selected. A stop command is active. To ensure that a motor
is connected to the drive, a permanent test current is applied to the motor.
Overvoltage control was activated by [2] Enabled in parameter 2-17 Over-voltage Control. The connected motor is
supplying the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in
controlled mode and to prevent the drive from tripping.
(For drives with a 24 V external supply installed only.) Mains supply to the drive is removed, but the control card is
supplied by the external 24 V.
Protection mode is active. The unit has detected a critical status (an overcurrent or overvoltage).
AQ262141314214en-000301 / 130R0880 | 133Danfoss A/S © 2021.11
Maintenance, Diagnostics, and
Troubleshooting
VLT® HVAC Drive FC 102
Operating Guide