6-61 Terminal X30/8 Min. Scale
Range: Function:
0 %* [0 -
200 %]
Scales the minimum output of the selected analog
signal on terminal X30/8. Scale the minimum
value as a percentage of the maximum signal
value. For example, enter the value 25% if the
output should be 0 mA at 25% of the maximum
output value. The value can never exceed the
corresponding setting in parameter 6-62 Terminal
X30/8 Max. Scale if the value is below 100%.
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is mounted in the frequency
converter.
6-62 Terminal X30/8 Max. Scale
Range: Function:
100
%*
[0 -
200 %
]
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the required maximum value of the current
signal output. Scale the output to give a lower
current than 20 mA at full scale, or 20 mA at an
output below 100% of the maximum signal value.
If 20 mA is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
that is 50%=20 mA. If a current 4–20 mA is
required at maximum output (100%), calculate
the percentage value as follows:
20mA/desiredmaximumcurrent × 100 %
i . e . 10mA:
20mA
10mA
× 100 % = 200 %
6-63 Terminal X30/8 Output Bus Control
Range: Function:
0 %* [0 - 100 %] Contains the value to apply to the output
terminal when it is congured as bus-
controlled.
6-64 Terminal X30/8 Output Timeout Preset
Range: Function:
0 %* [0 - 100 %] Contains the value to apply to the output
terminal when it is congured as bus-
controlled timeout and timeout is detected.
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
®
Extended Relay Card
MCB 113.
Option: Function:
[0] * No operation
[52] MCO 0-20mA/0-10V
[53] MCO 4-20mA
[100] Output freq. 0-100
[101] Reference Min-Max
[102] Feedback +-200%
[103] Motor cur. 0-Imax
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
®
Extended Relay Card
MCB 113.
Option: Function:
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[108] Torque +-160%
[109] Out frq 0-Fmax
[113] Ext. Closed Loop 1
[114] Ext. Closed Loop 2
[115] Ext. Closed Loop 3
[116] Cascade Reference
[117] Shaft Power
[118] Shaft Power 4-20mA
[130] Out frq 0-100 4-20mA
[131] Reference 4-20mA
[132] Feedback 4-20mA
[133] Motor cur. 4-20mA
[134] Torq.0-lim 4-20 mA
[135] Torq.0-nom 4-20mA
[136] Power 4-20mA
[137] Speed 4-20mA
[138] Torque 4-20mA
[139] Bus ctrl.
[140] Bus ctrl. 4-20 mA
[141] Bus ctrl t.o.
[142] Bus ctrl t.o. 4-20mA
[143] Ext. CL 1 4-20mA
[144] Ext. CL 2 4-20mA
[145] Ext. CL 3 4-20mA
[146] Cascade Ref. 4-20mA
[147] Main act val 0-20mA
[148] Main act val 4-20mA
[150] Out frq 0-Fmax 4-20mA
[156] Flow Rate
[157] Flow Rate 4-20mA
[254] DC Link 0-20mA
[255] DC Link 4-20mA
6-71 Terminal X45/1 Min. Scale
Enter the minimum scaling value of output of the analog signal
on terminal X45/1.
Range: Function:
0 %* [0 - 200 %]
6-72 Terminal X45/1 Max. Scale
Enter the maximum scaling value of output of the analog signal
on terminal X45/1.
Range: Function:
100 %* [0 - 200 %]
Parameter Description
VLT
®
AQUA Drive FC 202
98 Danfoss A/S © 05/2018 All rights reserved. MG20OB02