0-04 Operating State at Power-up
Option: Function:
Select the operating mode after reconnection of
the frequency converter to mains voltage after
power-down when operating in hand-on (local)
mode.
[0] * Resume Resumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition. The start/stop
condition is applied by [Hand On]/[O] on the
LCP or local start via a digital input as before
the frequency converter was powered down.
[1] Forced
stop,
ref=old
Stops the frequency converter, but at the same
time retains the local speed reference before
power-down in the memory. After mains
voltage is reconnected and after receiving a
start command (pressing [Hand On] or local
start command via a digital input), the
frequency converter restarts and operates at the
retained speed reference.
0-05 Local Mode Unit
Option: Function:
Denes if the local reference unit is shown
in terms of the motor shaft speed (in
RPM/Hz) or as percent.
[0] * As Motor
Speed Unit
[1] %
3.2.2 0-1* Set-up Operations
Dene and control the individual parameter set-ups.
The frequency converter has 4 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter exible in use and able to meet
the requirements of many dierent water system control
schemes often saving the cost of external control
equipment. For example, the set-ups can be used to
program the frequency converter to operate according to 1
control scheme in 1 set-up (for example daytime
operation) and another control scheme in another set-up
(for example night setback). Alternatively, they can be used
by an air handling unit or an OEM unit to identically
program all their factory-tted frequency converters for
dierent equipment models within a range to have the
same parameters. During production/commissioning, select
a specic set-up depending on the frequency converter
model.
Select the active set-up (that is, the set-up in which the
frequency converter is operating) in parameter 0-10 Active
Set-up. The LCP then shows the selected active set-up.
Using multi set-up, it is possible to switch between set-ups
with the frequency converter running or stopped, via
digital input, or serial communication commands (for
example for night setback). If it is necessary to change set-
ups while running, ensure that parameter 0-12 This Set-up
Linked to is programmed as required. For most water/
wastewater applications, it is not necessary to program
parameter 0-12 This Set-up Linked to even if change of set-
up is required when running. However, for complex
applications using the full exibility of the multiple set-ups,
it may be required. Using parameter 0-11 Programming Set-
up, it is possible to edit parameters within any of the set-
ups while continuing the frequency converter operation in
its active set-up. The active set-up can be a dierent set-up
to the one being edited. Using parameter 0-51 Set-up Copy,
it is possible to copy parameter settings between the set-
ups to enable quicker commissioning if similar parameter
settings are required in dierent set-ups.
0-10 Active Set-up
Option: Function:
Select the set-up in which the frequency
converter is to operate.
Use parameter 0-51 Set-up Copy to copy a set-up
to 1 or all other set-ups. To avoid conicting
settings of the same parameter within 2
dierent set-ups, link the set-ups using
parameter 0-12 This Set-up Linked to. Stop the
frequency converter before switching between
set-ups where parameters marked not
changeable during operation have dierent
values.
Parameters which are not changeable during
operation are marked FALSE in
chapter 4 Parameter Lists.
[0] Factory
setup
Cannot be changed. It contains the Danfoss
data set and can be used as a data source
when returning the other set-ups to a known
state.
[1]
*
Set-up 1 [1] Set-up 1 to [4] Set-up 4 are the 4 parameter
set-ups within which all parameters can be
programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-
up
Is used for remote set-up selections using digital
inputs and the serial communication port. This
set-up uses the settings from
parameter 0-12 This Set-up Linked to.
Parameter Description
VLT
®
AQUA Drive FC 202