1-90 Motor Thermal Protection
Option: Function:
[2] Thermistor
trip
Stops (trips) the frequency converter when the
connected thermistor or KTY sensor in the
motor reacts if motor overtemperature occurs.
The thermistor cutout value must be more
than 3 k.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3] ETR
warning 1
Calculates the load when set-up 1 is active
and activates a warning on the display when
the motor is overloaded. Program a warning
signal via 1 of the digital outputs.
[4] ETR trip 1 Calculates the load when set-up 1 is active
and stops (trips) the frequency converter
when the motor is overloaded. Program a
warning signal via 1 of the digital outputs. The
signal appears if there is a warning and if the
frequency converter trips (thermal warning).
[5] ETR
warning 2
[6] ETR trip 2
[7] ETR
warning 3
[8] ETR trip 3
[9] ETR
warning 4
[10] ETR trip 4
[20] ATEX ETR Activates the thermal monitoring function for
Ex-e motors for ATEX. Enables
parameter 1-94 ATEX ETR cur.lim. speed
reduction, parameter 1-98 ATEX ETR interpol.
points freq., and parameter 1-99 ATEX ETR
interpol points current.
NOTICE
If [20] ATEX ETR is selected, follow the instructions in the
dedicated chapter of the design guide and the
instructions provided by the motor manufacturer.
NOTICE
If [20] ATEX ETR is selected, set parameter 4-18 Current
Limit to 150%.
3.3.15 PTC Thermistor Connection
1330
550
250
-20 °C
175HA183.11
4000
3000
R
(Ω)
nominal
nominal -5 °C nominal +5 °C
[°C]
Illustration 3.12 PTC Prole
Using a digital input and 10 V as supply:
Example: The frequency converter trips when the motor
temperature is too high.
Parameter set-up:
Set parameter 1-90 Motor Thermal Protection to [2]
Thermistor Trip.
Set parameter 1-93 Thermistor Source to [6] Digital
Input.
PTC / Thermistor
R
OFF
ON
<800 Ω
+10V
130BA152.10
>2.7 kΩ
12 13 18 37322719 29 33 20
5550
39 42 53 54
Illustration 3.13 PTC Thermistor Connection - Digital Input
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 59
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals